Detailed Description
WARNING | |
---|---|
Description of system words %SW128 to %SW152 on Momentum processors
Word
|
Function |
Description |
Initial State |
---|---|---|---|
%SW128... %SW129
|
I/O-Bus module health |
%SW128.0 is module #1 health; %SW129.15 is module #32 health. If a health bit is set to:
|
0 |
%SW132
|
I/O compatibility detected error status |
NOTE: The content of this
word is significant only if %S118 is set to 1.
Meaning of the different bits of the word %SW132.0 to %SW132.15:
|
0 |
%SW134
|
I/O-Bus detected error |
Meaning of the values of the word %SW134:
NOTE: %SW134 stores the last detected error. The
system does not automatically reset this word to 0 when the cause
of the detected error o longer exists. You need to set this word to
0 after resolving the cause of the detected error.
|
0 |
%SW135
|
Local I/O detected error |
Meaning of the values of the word %SW135:
NOTE: %SW135 stores the last detected error. The
system does not automatically reset this word to 0 when the cause
of the detected error o longer exists. You need to set this word to
0 after resolving the cause of the detected error.
|
0 |
%SW137
|
Modbus slave address - serial port 2 |
Read-only system word containing the Modbus slave address for serial port number 2. NOTE: Applies to Momentum processors with 2 serial ports, for example the
171 CBU 78090.
|
0 |
%SW138
|
Messages transmitted - serial port 2 |
Read-only system word containing the number of messages transmitted to serial port number 2. NOTE: Applies to Momentum processors with 2 serial ports, for
example the 171 CBU 78090.
|
0 |
%SW139
|
Messages received - serial port 2 |
Read-only system word containing the number of messages received by serial port number 2. NOTE: Applies to Momentum processors with 2 serial ports, for
example the 171 CBU 78090.
|
0 |
%SW141... %SW142
|
IP netmask |
These words contain the following data:
NOTE: Applies to Momentum processors with an Ethernet
port, for example the 171 CBU 98090 and 171 CBU 98091.
|
0 |
%SW143... %SW144
|
IP gateway |
These words contain the following data:
NOTE: Applies to Momentum processors with an Ethernet
port, for example the 171 CBU 98090 and 171 CBU 98091.
|
0 |
%SW145... %SW147
|
MAC address |
These words contain the following data:
NOTE: Applies to Momentum processors with an Ethernet
port, for example the 171 CBU 98090 and 171 CBU 98091.
|
0 |
%SW148
|
ETH services status |
These words contain the following data:
|
0 |
%SW151... %SW152
|
ETH open connection number |
These words contain the following data:
|
0 |