IEC61850 Explicit Messaging Detected Error Codes
(Original Document)
Introduction
If an MBP_MSTR function block does not execute an explicit message, Control Expert displays a hexidecimal detected error code.
Refer to the topic TCP/IP Ethernet detected error codes for a description of those codes.
IEC61850 Detected Error Codes
IEC61850 hexadecimal detected error codes include:
Code (hexadecimal)
Description
16#800D
Timeout on the explicit message request
16#8015
Either:
  • Nor resources to handle the message, or
  • Internal event: no buffer available, no link available, impossible to send to the TCP task
16#8018
Either:
  • Another explicit message for this device is in progress, or
  • TCP connection or encapsulation session in progress
16#8030
Timeout on the Forward_Open request
Note: The following 16#81xx events are Forward_Open response detected error codes that originate at the remote target and are received via the CIP connection.
16#8100
Connection in use or duplicate Forward_Open
16#8103
Transport class and trigger combination not supported
16#8106
Ownership conflict
16#8107
Target connection not found
16#8108
Invalid network connection parameter
16#8109
Invalid connection size
16#8110
Target for connection not configured
16#8111
RPI not supported
16#8113
Out of connections
16#8114
Vendor ID or product code mismatch
16#8115
Product type mismatch
16#8116
Revision mismatch
16#8117
Invalid produced or consumed application path
16#8118
Invalid or inconsistent configuration application path
16#8119
Non-Listen Only connection not opened
16#811A
Target object out of connections
16#811B
RPI is smaller than the production inhibit time
16#8123
Connection timed out
16#8124
Unconnected request timed out
16#8125
Parameter event in unconnected request and service
16#8126
Message too large for unconnected_send service
16#8127
Unconnected acknowledge without reply
16#8131
No buffer memory available
16#8132
Network bandwidth not available for data
16#8133
No consumed connection ID filter available
16#8134
Not configured to send scheduled priority data
16#8135
Schedule signature mismatch
16#8136
Schedule signature validation not possible
16#8141
Port not available
16#8142
Link address not valid
16#8145
Invalid segment in connection path
16#8146
Event in Forward_Close service connection path
16#8147
Scheduling not specified
16#8148
Link address to self invalid
16#8149
Secondary resources unavailable
16#814A
Rack connection already established
16#814B
Module connection already established
16#814C
Miscellaneous
16#814D
Redundant connection mismatch
16#814E
No more user-configurable link consumer resources: the configured number of resources for a producing application has reached the limit
16#814F
No more user-configurable link consumer resources: there are no consumers configured for a producing application to use
16#8160
Vendor specific
16#8170
No target application data available
16#8171
No originator application data available
16#8173
Not configured for off-subnet multicast
16#81A0
Event in data assignment
16#81B0
Optional object state event
16#81C0
Optional device state event
Note: All 16#82xx events are register session response detected error codes.
16#8200
Target device does not have sufficient resources
16#8208
Target device does not recognize message encapsulation header
16#820F
Reserved or unknown event from target