UL (UL61010)
|
CSA (CSA22.2 no. 142)
|
RCM
|
Hazardous locations (Cl1 div 2)
|
IEC61000-4-16
|
EMI EN 55011
|
CE
|
EN 61131-1
|
IEC 61131-2 (zone B and zone C, except surges on AC: zone B only)
|
Key
|
Certification Body
|
Country
|
---|---|---|
ABS
|
American Bureau of Shipping
|
United States
|
BV
|
Bureau Veritas
|
France
|
DNV
|
Det Norske Veritas
|
Norway
|
GL
|
Germanischer Lloyd
|
Germany
|
LR
|
Lloyd's Register
|
United Kingdom
|
RINA
|
Registro Italiano Navale
|
Italy
|
Parameter
|
Reference
|
Specification
|
---|---|---|
protection
|
EN 61131-2
|
IP20
|
IEC 60527
|
||
protection class
|
EN 61131-2
|
protection class 1
|
over voltage class
|
EN 61131-2
|
category II
|
operating temperature
|
IEC 60068-2-1
|
0 ... 60° C
|
Ab&Ad (cold)
|
||
IEC 60068-2-2
|
||
Bb&Bd (cold)
|
||
storage temperature
|
IEC 60068-2-1
|
-40 ... 85° C
|
Ab&Ad (cold)
|
||
IEC 60068-2-2
|
||
Bb&Bd (cold)
|
||
sinusoidal vibration
|
IEC 60068-2-6fC
|
|
EN 61131-2
|
||
operating shock
|
IEC 60068-2-27Ea
|
15 g peak, 11 ms, half-sine wave, 3 shocks in each direction (+ and -) for each of the 3 principle axes
|
altitude
|
–
|
0 ... 5000 m maximum during operation. For altitudes > 2000 m, reduce the operating temperature by 6° C for each additional 1000 m.
|
free fall, random (packaged)
|
EN 61131-2
|
5 random drops from 1 m onto flat surfaces
|
IEC 60068-2-32
|
||
test ed., method 1
|
||
free fall, flat drop (unpackaged)
|
EN 61131-2
|
|
IEC 60068-2-32
|
||
test ed., method 1
|
||
free fall, angled (unpackaged)
|
EN 61131-2
|
5 drops from 0.1 m onto each corner
|
IEC 60068-2-31
|
||
relative humidity (operating)
|
IEC 60068-2-78Ca
|
93% (+/- 2%, noncondensing) at 60° C
|
relative humidity (nonoperating)
|
IEC 60068
|
93% (+/- 2%, noncondensing) at 60° C
|