Module Debugging Screen
Original instructions
Introduction
Use the debugging screen to diagnose an Ethernet port on the BMENOR2200H module.
Parameters
Find these parameters on the Debug tab:
Field
Description
MAC address
BMENOR2200H module’s MAC address
IP address
BMENOR2200H module’s IP address
Subnetwork mask
BMENOR2200H module’s subnetwork mask address
Gateway address
BMENOR2200H module’s gateway address
LED Display
Observe these LEDs for conditions related to the module:
Location
LED
Description
upper-right window corner
Run
on: The module is operating normally.
off: The PLC is not configured.
Err.
on: A configuration or system error is detected.
off: The module is operating normally.
Fault tab
Fault
Fault descriptions:
  • %MW2.4: detected internal fault
  • %MW2.5: detected configuration fault
  • %MW2.6: detected communication error
  • %MW2.7: detected application fault
  • %MW2.8: detected configuration error
  • %MW2.9: Ethernet disabled
  • %MW2.10: duplicate IP address
  • %MW2.12: link disconnection
  • %MW2.13: awaiting IP address
  • %MW2.14: storm detection