The BMENOR2200H module’s event backup buffer can store events when power to the module stops.
Event Backup Characteristics
You can configure the module for the events or data types that are saved upon a loss of power or a module hot-swap.
These are the capacities for event storage for the BMENOR2200H module and the RTU protocol:
-
event buffer:
-
The module saves up to 10,000 events in the event buffer upon a loss of power.
-
The module saves up to 10,000 security events per server channel in the event buffer.
-
flash memory:
NOTE: You can enable or disable the exchange of unsolicited messaging data.
Retain or Clear the Buffer
The event buffer in RAM is retained in these situations:
The event buffer in RAM is cleared in these situations:
-
Use a SCADA command to clear the buffer in RAM.
-
The CPU experiences a cold restart (such as during the download of a new configuration) or you press the reset button on the power supply. All communications are reset.
-
The CPU experiences a cold restart (such as during the download of a new configuration), and communications are reset.
-
Change the DNP3 cyber security configuration on the web page to clear the buffer.
-
A SCADA command specifically clears the buffer.
The BMENOR2200H module has different backup behaviors in different cases. The type of case is defined from the user point view:
|
Case
|
Description
|
Event
|
1
|
Loss of power
|
power lost
|
Saves events in non-volatile memory on loss of power.
|
2
|
Power start
|
power on/restore
|
Restores events when the RTU protocol starts.
|
3
|
Protocol restart
|
These actions clear the module event buffer:
|
Does not save events when the protocol exits.
|
The BMENOR2200H module scans and stores events in each channel one by one when the number of events exceeds the Flash memory capacity, the module saves only the latest events.