140 CRA 93x 00 Update Prerequisites
 
Overview
The 140 CRA 93• 00 update is performed using OS Loader software via a Modbus or Modbus Plus physical connection, and a 140 CRP 93• 00 head module.
Update Operation and Associated Connections
Main operations performed to update a 140 CRA 93• 00 module:
Operation
Communication protocol
Connect the PC to the Modbus or Modbus Plus port of the CPU.
Modbus
Modbus Plus
Update the 140 CRA 93• 00 module firmware.
Compatibility Rules
The update of a 140 CRA 93• 00 module via a 140 NRP 954 01C repeater may not be possible as indicated in the following table:
CRA module reference
Product version
Remote OS update via 140 NRP 954 01C repeater
140 CRA 93• 00
≤ 08
Yes
≥ 09
No
NOTE: For CRA modules with a product version 09, update the software version of the CRA module from 2.0 to 2.01 before using a 140 NRP 954 01C repeater in the S908 RIO network.
Physical Connection