Stage
|
Description
|
---|---|
1
|
Download and install Unity Loader software.
|
2
|
Configure and store IP parameters (optional).
|
3
|
Connect your configuration PC to the EIO adapter.
|
4
|
Transfer the firmware update to the EIO adapter or the Ethernet backplane.
|
Step
|
Action
|
---|---|
1
|
Enter the web address for Schneider Electric (www.schneider-electric.com) in an Internet browser.
|
2
|
In the Search from input field, enter the phrase Unity Loader and press Enter.
|
3
|
Examine the search results and select the appropriate entry for the Unity Loader software.
|
4
|
Follow the on-screen instructions to download both the Unity Loader installation software and any necessary installation instructions.
|
5
|
Run the Unity Loader setup file and follow the instructions (on the screen and in the downloaded documentation) to install Unity Loader.
|
Parameter
|
Description
|
---|---|
Default IP Address
|
The default IP address starts with 10.10 and uses the last 2 bytes of the MAC address. As an example, a device with the MAC address of 00:00:54:10:8A:05 has a default IP address of 10.10.138.5 (0x8A=138, 0x05=5).
|
Default Sub-Network Mask
|
The default mask is 255.0.0.0 (a class A mask).
|
Default Gateway Address
|
The default gateway address is identical to the default IP address.
|
Step
|
Action
|
---|---|
1
|
Start or re-start the adapter with the rotary switch set toStored.
|
2
|
Store the IP address by sending a explicit message to the TCP/IP Interface Object (Attribute ID 05: Interface Configuration).
|
Step
|
Action
|
Comment
|
---|---|---|
1
|
Open a command window on the PC.
|
Start → Run.
|
2
|
In the Run dialog, type in cmd.
|
|
3
|
Click OK.
|
|
4
|
At the command prompt, type in the ping command and the device IP address.
|
Example: C:\>ping 192.168.21.38:
|
5
|
The command window verifies that a connection is established.
|
Example: Reply from 192.168.21.38...
|
Step
|
Action
|
---|---|
1
|
Open Unity Loader on your PC. (Start → Programs → Schneider Electric → Unity Loader)
Result: Unity Loader opens and displays the Project tab.
|
2
|
At the bottom of the tab in the Connection area, connect to the module:
|
3
|
After Unity Loader has connected to the module, click the Firmware tab in the Unity Loader dialog.
|
4
|
In the PC area, click the ellipsis (...) button to open a dialog where you can navigate to and select the firmware file for the adapter module. The firmware is contained in a Unity Loader file (.LDX extension).
NOTE: When using the BMECRA31210, you can also update firmware for a BMEXBP••00. After you select the firmware file and close the dialog, the selected revision of this firmware is displayed in the list on the left, and the current version of the firmware is displayed in the list on the right.
|
5
|
When the arrow in the middle of the Unity Loader dialog is green, click Transfer.
NOTE: Only click Transfer if the arrow is green. A yellow arrow indicates that the firmware file on your computer is the same version or newer than the file selected for transfer; a red arrow indicates that the firmware on the computer is not compatible with the EIO adapter. |
6
|
Click Yes on the 2 dialogs that appear.
|
7
|
The Transferring data to PLC opens, which indicates the transfer status with the blue bars at the bottom of the screen.
|
8
|
After the transfer is complete, click Close.
|
9
|
In the Unity Loader software, click Disconnect and close the window.
|
10
|
Reboot the module to finalize the firmware update.
|