(%MWx + 8) Command Word Function
|
Command word bits (Control Expert-IEC bit order) that must be set to 1
|
Command word bits (Control Expert-IEC bit order) that must be set to 0
|
---|---|---|
Terminated ASCII input (Bit 11 = 1)
|
4, 5, 6, 7, 13, 14
|
0, 1, 2, 3, 8, 9, 10
|
Simple ASCII input (Bit 10 = 1)
|
4, 5, 6, 7, 13, 14
|
0, 1, 2, 3, 8, 9, 11
|
Simple ASCII output (Bit 9 = 1)
|
4, 5, 6, 7, 13, 14
|
0, 1, 2, 3, 8, 10, 11
|
Modem output (Bit 9 = 1)
|
0, 1, 2, 3, 13, 14
|
4, 5, 6, 7, 8, 10, 11
(plus one, but ONLY one, of the following bits is set to 1: 0, 1, 2 or 3, while the other three bits must be set to 0)
|
Modbus master messaging output
(Bit 8 = 1)
|
13,14
|
0, 1, 2, 3, 4, 5, 6, 7, 9, 10, 11
|
Enable ASCII receive input FIFO ONLY (Bit 7 = 1)
|
4,5, 6, 13, 14
|
0, 1, 2, 3, 8, 9, 10, 11
|