Module TBX DMS 16S44
|
||
---|---|---|
Nominal voltage
|
120 V AC
|
|
Nominal current
|
15 mA
|
|
Sensor power supply
(including ripple)
|
93 at 132 V AC
|
|
Voltage for ON state
|
>74 V
|
|
Current at 74 V
|
6 mA
|
|
Voltage for OFF state
|
< 20 V
|
|
Current for OFF state
|
< 4 mA
|
|
Input impedance
|
10 kΩ
|
|
Switch-on time
(change from 0 to 1)
|
5 ms
|
|
Switch-off time
(change from 1 to 0)
|
5 ms
|
|
Permitted line resistance (2 wire proximity sensor)
|
< 100 Ω
|
|
Permitted line resistance (volt-free contact)
|
< 500 Ω
|
|
Permitted leakage resistance (2 wire proximity sensor)
|
> 100 Ω
|
|
Permitted leakage resistance (volt-free contact)
|
> 30 Ω
|
|
IEC standard 1131
|
Type 2
|
|
Compatibility with CENELEC 2 wire proximity sensors
|
Yes
|
|
Type of input
|
Capacitive
|
|
Type of logic
|
Positive
|
|
Sensor common
|
At the supply phase
|
Module TBX DMS 16S44
|
|
---|---|
Nominal voltage
|
120 V AC
|
Nominal current at 25 °C
|
1 A
|
Frequency
|
50/60 Hz
|
Supply voltage limits
|
93 at 132 V AC
|
Current at 60 °C
|
0,5 A
|
Peak current at switch-on
|
12 A (1 cycle)
|
Voltage for ON state
|
> 80 V
|
Voltage for OFF state
|
< 20 V
|
Leakage current at OFF state
|
< 3 mA
|
Residual voltage at ON state
|
< 1,5 V
|
Switching time at ON state
|
≤ 80 ms
|
Switching time at OFF state
|
≤ 20 ms
|
Protection against overloads and short‐circuits
|
Yes: internal fuse
|
Protection against inductive overvoltages
|
No, (provide an RC or GMOV)
|
Conforms to IEC 1131
|
Yes
|
Compatible with DC inputs
|
No
|
Type of logic
|
Positive
|
Sensor common
|
At the supply phase
|
Isolation between channels or groups of channels and internal bus
|
1500 V rms. 50 - 60 Hz
|