TBX DSS 1625
|
||
---|---|---|
Nominal voltage +SV
|
24 V DC
|
|
Supply voltage +SV
|
19,2 V DC to 30 V DC
|
|
Current drawn on +SV of the base module (at 24 V)
(with 60 % of the relays active)
|
if basic unit
|
125 mA typically
|
if extension base unit
|
negligible
|
|
Current drawn at +SV by extension module (at 24 V)
(with 60 % of the relays active)
|
115 mA typically
|
|
Immunity to +SV microbreaks
(with 60 % of the relays active)
|
10 ms
|
|
Power dissipated at nominal load in the module
(with 60 % of the relays active)
|
3,1 W at 24 V
|
|
Dielectric strength between inputs and ground (GND)
|
1500 V rms - 50/60 Hz for 1 min
|
|
Isolation resistance
|
> 10 MΩ below 500 V DC
|
|
Key:
|
||
SV
|
Power supply to module (communication module if present and input interfaces).
|