TBX DMS 1625 (1)
|
||
---|---|---|
Nominal voltage
|
24 V DC
|
|
Supply voltage +SV
|
19,2 V DC to 30 V DC
|
|
Current drawn on +SV of the base module (at 24 V)
|
if basic unit
|
80 mA typically
|
if extension base unit
|
70 mA typically
|
|
Current drawn at +SV by extension module (at 24 V)
|
10 mA typically
|
|
Current drawn at +IS (at 24 V)
(loading = 60 %)
|
75 mA typically
|
|
Power dissipated at nominal load in the module
(loading = 60 %)
|
3,7 W at 24 V
|
|
Dielectric strength between inputs and ground (GND)
|
1500 V rms - 50/60 Hz for 1 min
|
|
Isolation resistance
|
> 10 MΩ below 500 V DC
|
|
Key:
|
||
SV
|
Power supply to module (communication module if present and input/output interfaces).
|
|
IS
|
Power supply to sensors.
|
|
(1)
|
For a configuration comprising 2 TBX DMS 1625 base units, the maximum ambient temperature is 40 °C, if the 2 base units are used at 100 % (16 ON relays).
|