Module TBX DES 1622
|
|
---|---|
Nominal voltage IS
|
24 V DC
|
Current at 24 V
|
15 mA
|
Sensor power supply IS
|
19.2 V DC to 30 V DC
|
Voltage for ON state
|
≥ 11 V
|
Current at 11 V
|
≥ 6 mA
|
Voltage for OFF state
|
< 5 V
|
Current for OFF state
|
≤ 2 mA
|
Input impedance
|
1.6 kΩ
|
Switch-on time
|
7 to 15.5 ms
|
Switch-off time
|
7 to 15.5 ms
|
Permitted line resistance (2 wire proximity sensor)
|
100 Ω
|
Permitted line resistance (volt-free contact)
|
500 Ω
|
Permitted leakage resistance (2 wire proximity sensor)
|
> 100 kΩ
|
Permitted leakage resistance (volt-free contact)
|
> 30 kΩ
|
IEC standard 1131
|
Type 2
|
Compatibility with Telemecanique 2 wire proximity sensors
|
Yes
|
Compatibility with CENELEC 3 wire proximity sensors
|
Yes
|
Compatible with TBX transistor outputs
|
Yes
|
Type of input
|
Resistive
|
Type of logic
|
Positive
|
Power dissipated per channel at ON state
|
0,36 W
|
Protection of +C terminals against overload or short-circuit
|
No
|
Protection against a reverse polarity on IS
|
Yes: reverse diode in parallel (ext. fuse 2 A (quick blow))
|
Key:
|
|
IS
|
Power supply to sensors.
|