TBX module power consumption table
(Original Document)
Power consumption table
The following table shows the power consumption table for the TBX modules.
Module part (1)
Sensor part
If base module
If extension module
If base module or extension module
on +SV base
on +SV base
on +SV ext.
on +S or +IS
on S, +OS or preact. supply
TBX LEP 020 (2)
with a 24 V supply
70 mA
-
-
-
-
TBX LEP 030 (2)
with a 24 V supply
70 mA
-
-
-
-
TBX CEP 1622
90 mA
-
-
70 mA
-
TBX CSP 1622
100 mA
-
-
-
35 mA (3)
TBX CSP 1625
195 mA
-
-
-
-
TBX EEP 08C22
190 mA
-
-
-
120 mA (4)
TBX ESP 08C22
107 mA
negligible
107 mA
-
98 mA (3)
TBX EEP 1622
240 mA
-
-
-
208 mA (5)
TBX ESP 1622
107 mA
negligible
107 mA
-
51 mA (3)
TBX DES 1622
20 mA
negligible
15 mA
150 mA
-
TBX DES 16C22
40 mA
10 mA
30 mA
70 mA
-
TBX DES 16F22
40 mA
10 mA
30 mA
70 mA
-
TBX DES 1633
20 mA
negligible
16 mA
70 mA
-
TBX DMS 16C22
40 mA
10 mA
30 mA
35 mA
25 mA (3)
TBX DMS 16P22
30 mA
negligible
25 mA
75 mA
100 mA
TBX DMS 16C222
45 mA
10 mA
35 mA
35 mA
25 mA (3)
TBX DMS 1025
35 mA
10 mA
25 mA
75 mA
-
TBX DMS 1625
80 mA
10 mA
70 mA
75 mA
-
TBX DSS 1622
30 mA
negligible
25 mA
-
35 mA (3)
TBX DSS 16C22
30 mA
negligible
25 mA
-
45 mA (3)
TBX DSS 1625
125 mA
negligible
115 mA
-
-
TBX DSS 1235 (2)
130 mA
negligible
125 mA
-
-
TBX DES 16S04
60 mA
negligible
55 mA
70 mA
-
TBX DMS 16S44
60 mA
negligible
55 mA
75 mA
-
TBX AES 400
130 mA
negligible
130 mA
-
-
TBX ASS 200
180 mA
15 mA
162 mA
-
-
TBX AMS 620
224 mA
59 mA
162 mA
-
-
Key:
(1)
These consumptions correspond to a typical a 24 V module power supply, with a 60 % loading (except for TBX DES 1633 which is supplied with a 48 V V).
(2)
With a 48 V power supply, divide the values by 2.
(3)
Module consumption, loads not included.
(4)
Leakage current/sensor 15 mA max.
(5)
Leakage current/sensor 13 mA max.