Step
|
Action
|
---|---|
1
|
Access the calibration adjustment screen
|
2
|
Double-click on channel 0.
Result: the question ‘Switch to recalibration mode?’ appears.
|
3
|
Answer Yes to the above question.
Result: the question ‘Perform 0 calibration?’ appears.
|
4
|
Place a shunt on all inputs of the module to perform 0 calibration, and answer Yes to the above question.
Otherwise, answer No not to perform 0 calibration.
|
5
|
You can then perform full scale calibration.
Depending on the range to calibrate, connect a reference voltage to the voltage input of channel 0:
Warning: the reference 5 V is used to recalibrate the entire measurement string for ranges 0..20 mA and 4..20 mA, except for the 250 Ohm current shunt on the current input.
|
6
|
Once the reference is connected to the voltage input (for example 10 V), use the Reference drop-down list to select this value. You may have to wait while the connected reference voltage stabilizes, then confirm the selection by clicking the command button Confirm. The ranges connected to this reference voltage (for example 10 V and 0..10 V) are calibrated automatically.
|
7
|
You may have to calibrate the module for the other ranges.
The command button Return To Factory Parameters is used to cancel all calibrations previously performed and return to the initial factory calibration.
|
8
|
Press the command button Save to acknowledge and save the new calibration to the module. When you quit the calibration screen without saving, a message appears to inform you that the calibration operations will be lost
|