Measurement Filtering
(Original Document)
Introduction
The system uses first order filtering. The filtering coefficient can be modified from a programming console or via the program.
Mathematical Formula
The mathematical formula used is as follows:
where:
α = efficiency of the filter,
Mesf(n) = measurement filtered at moment n,
Mesf(n-1) = measurement filtered at moment n-1,
Valg(n) = gross value at moment n.
On configuration, you can select the filtering value from a choice of 7 values.
Values for the Module TBX AES 400
The filtering values are as follows, and depend on mains voltage:
Effectiveness
Value
Corresponding α
Rejection time constant at 50 Hz
Rejection time constant at 60 Hz
No filtering
0
0
0
0
Low filtering
1
2
0.750
0.875
1.6 s
3.2 s
1.4s
2.7s
Medium filtering
3
4
0.937
0.969
6.4 s
12.8 s
5.4 s
10.8 s
High filtering
5
6
0.984
0.992
25.6 s
51.2 s
21.1 s
43.5 s