Mode
|
Meaning
|
---|---|
Fallback
|
The channels are set to 0 or 1 depending on the fallback value set for the group of 8 corresponding channels.
|
Maintain
|
The outputs remain in the status they were in before switching to Stop.
|
![]() |
UNEXPECTED APPLICATION BEHAVIOR
Ensure that the extension module is connected to the base module via the connection cable, else the extension module outputs would not switch to fallback mode.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
Step
|
Action
|
---|---|
1
|
Access the hardware configuration screen of the required module.
|
2
|
In the channel area, select the required channel group.
|
3
|
In the General parameters area, click on the drop-down menu button in the Fallback mode field.
Result: a drop-down list appears.
![]() |
4
|
Select the required fallback mode.
|
5
|
For the Fallback mode, configure each channel of the selected group.
To do this, click on the drop-down menu button in the Fallback value column of the configuration area.
|
6
|
Click on the required value (0 or 1).
|