Parameters of the Remote TBX Discrete Inputs on the Fipio Bus
(Original Document)
At a Glance
The Discrete TBX inputs on the Fipio bus feature parameters for each channel, each group of 8 channels, or for all channels.
Parameters
The table below shows the parameters available for each TBX discrete input module.
Module reference
No. of inputs
Associated task (for the module)
Filtering
Latching (per channel)
Wire test (per channel)
TBX CEP 1622
16
Mast / Fast
-
-
-
TBX DES 1622
16
Mast / Fast
-
-
-
TBX DES 1633
16
Mast / Fast
-
-
-
TBX EEP 1622
16
Mast / Fast
-
-
-
TBX DMS 1025
8 (inputs)
Mast / Fast
-
-
-
TBX DMS 1625
8 (inputs)
Mast / Fast
-
-
-
TBX DES 16S04
16
Mast / Fast
-
-
-
TBX DMS 16S44
(1)
Mast / Fast
-
-
-
TBX DMS 16P22
8 (inputs)
Mast / Fast
-
-
-
TBX DES 16C22
16
Mast / Fast
-
-
Active / Inactive (2)
TBX EEP 08C22
16
Mast / Fast
-
-
Active / Inactive (2)
TBX DMS 16C22
8
Mast / Fast
-
-
Active / Inactive (2)
TBX DMS 16C222
8
Mast / Fast
-
-
Active / Inactive (2)
TBX DES 16F22
16
Mast / Fast
Normal / Fast
Active / Inactive (2)
-
Legend:
(1)
8 input channels + 8 programmable input/output channels.
(2)
Check box.