Displaying measurements on inputs
(Original Document)
Introduction
This process is used to select the display format depending on which formats are provided in the user program.
Standardized display of electrical ranges
The values are displayed in standardized units (in % with 2 decimals, also with symbol °/):
Type of range
Display
unipolar range
0-10V, 0-5V, 0-20mA, 4-20mA
from 0 to 10000 (0 °/ to 10000 °/).
bipolar range
+/-10V
from -10000 to +10000 (-10.000 °/ to +10.000 °/).
User-defined display of electrical ranges
The user can select the value range in which the measurements are expressed, by selecting:
The minimum and maximum limits are between -31128 and +31128.
Example:
Use of a 2/20 bar pressure sensor supplying a 0/20 mA signal and having a linear characteristic.
The user is interested in the pressure rather than the current value. The best resolution is obtained by selecting user display:
The user-program then uses values expressed directly in the physical unit, the millibar.
Illustration: