Introduction
After you create a Control Expert project that includes a 140CRA31908 adapter module, use these instructions to download the application to the M580 PLC.
Connection
Download the Control Expert application to the PLC through one of the ports on the M580 CPU or through a connection to an Ethernet communication module:
Method
Connection
USB port
If the PLC and the PC that is running Control Expert both have USB ports, you can download the application to the PLC directly through the USB ports.
Ethernet port
If the PLC and the PC that is running Control Expert both have Ethernet ports, you can download the application to the PLC directly through the Ethernet ports.
communication module
You can download the application to the PLC by connecting Control Expert to the IP address of the communication module.
Download the Application to the PLC
Download the Control Expert application to the M580 PLC:
Step
Action
1
Open the Control Expert project.
2
Double-click PLC bus in the Project Browser.
3
Double-click the ports on the M580 CPU in the PLC bus rack.
4
Select the Security tab.
5
Click the Unlock Security button to set the communication protocol services to Enabled.
6
Build the project (Build → Rebuild All Project).
7
Open the Set Address window (PLC → Set Address).
8
In the Address pull-down menu, select the IP address of the CPU.
9
In the Media pull-down menu, select the media type used to connect to the CPU (USB or Ethernet).
NOTE: Select the Test Connection button to execute a connection test.
10
Press OK to apply the selections.
11
Connect the PLC to the project (PLC → Connect).
12
Open the Transfer Project to PLC window (PLC → Transfer Project to PLC).
13
Click OK to confirm a stop on the project while the application downloads.
NOTE: To confirm the download, check PLC Run after Transfer and press the Transfer button.