S908 Network Limitations in an M580 System
Original instructions
Introduction
M580 architectures with X80 remote drops that include a 140CRA31908 adapter module observe the limitations described below.
Limitations
Observe these limitations:
Function
Support
Comment
CCOTF
none
There is no support to add or delete X80 remote drops that contain a 140CRA31908 adapter module.
I/O Sniffing
none
I/O sniffing is not supported by M580 architectures.
I/O vision
state RAM
The state RAM and topological I/O vision are supported to program the I/O over the S908 network. The device DDT is not supported.
Quantum Safety modules
none
Quantum Safety modules can be configured in the M580 network only when they are managed by a Quantum Safety PLC.
section scheduler
none
The 140CRA31908 module does not support the section scheduler mechanism.
segment scheduler
none
The 140CRA31908 module does not support the segment scheduler mechanism.
used task
MAST only
Only the MAST task can process the I/Os over S908. The 140CRA31908 module, therefore, supports the MAST task for only the I/O modules configured in its local rack.
200 Series
with adapter
M580 architectures support 200 Series I/O when the P451 or P453 interface is adapted with a J290 or J291 S908 I/O adapter.
NOTE: In the M580 configuration, assign at least one Quantum S908 remote drop with address 2, 3, 4, 5, 6, 7, 8 or 9.