Introduction
The addressing method of data associated with controller input/output depends on the platform, I/O location, and topology.
A summary of addressing methods is provided for the following platforms:
Modicon M580
For information about the Modicon M580 application memory structure, refer to the chapter on BME P58 xxxx CPU Memory Structure.
Data addressing method allowed depending on the module location in the architecture:
Addressing (addressing example) |
Local rack |
RIO Drop |
DIO |
CANopen |
ASI |
Profibus |
||||
EIO x80 |
EIO Quantum |
S908 |
||||||||
Located I/O |
||||||||||
Topological Addressing |
Topological (%lr.m.c) |
X |
– |
– |
X |
– |
– |
X |
– |
|
IODDT (%CHr.m.c) |
X |
– |
– |
X |
– |
– |
X |
– |
||
Flat or Modbus Addressing |
State RAM (%lx) |
– |
– |
X |
X |
– |
– |
– |
– |
|
Located Memory (%MWx) |
– |
– |
X |
X |
– |
– |
– |
– |
||
Unlocated I/O |
||||||||||
Device DDT |
X |
X |
X |
– |
X |
X |
X |
X |
||
X Allowed addressing method. – Not allowed addressing method. |
Modicon M340
Data addressing method allowed depending on the module location in the architecture:
Addressing (addressing example) |
Local rack |
DIO (NOE scan) |
DIO (NOC scan) |
CANopen |
ASI |
Profibus |
||
Located I/O |
||||||||
Topological Addressing |
Topological (%lr.m.c) |
X |
– |
– |
X |
X |
– |
|
IODDT (%CHr.m.c) |
X |
– |
– |
X |
X |
– |
||
Flat or Modbus Addressing |
State RAM (%lx) |
X |
– |
– |
– |
– |
– |
|
Located Memory (%MWx) |
X |
X |
X |
X |
– |
X |
||
Unlocated I/O |
||||||||
Device DDT |
– |
– |
– |
– |
– |
– |
||
X Allowed addressing method. – Not allowed addressing method. |
Modicon Quantum
Data addressing method allowed depending on the module location in the architecture:
Addressing (addressing example) |
Local rack |
RIO Drop |
DIO (NOE scan) |
DIO (NOC scan) |
||||
EIO x80 |
EIO Quantum |
S908 |
||||||
Located I/O |
||||||||
Topological Addressing |
Topological (%lr.m.c) |
X |
– |
– |
X |
– |
– |
|
IODDT (%CHr.m.c) |
X |
– |
– |
X |
– |
– |
||
Flat or Modbus Addressing |
State RAM (%lx) |
X |
– |
X |
X |
X |
– |
|
Located Memory (%MWx) |
X |
– |
X |
X |
X |
X |
||
Unlocated I/O |
||||||||
Device DDT |
– |
X |
– |
– |
– |
– |
||
X Allowed addressing method. – Not allowed addressing method. |
Modicon Premium
Data addressing method allowed depending on the module location in the architecture:
Addressing (addressing example) |
Local rack |
DIO (ETY scan) |
DIO (ETC scan) |
CANopen |
||
Located I/O |
||||||
Topological Addressing |
Topological (%lr.m.c) |
X |
– |
– |
– |
|
IODDT (%CHr.m.c) |
X |
– |
– |
– |
||
Flat or Modbus Addressing |
State RAM (%lx) |
– |
– |
– |
– |
|
Located Memory (%MWx) |
– |
X |
X |
X |
||
Unlocated I/O |
||||||
Device DDT |
– |
– |
– |
– |
||
X Allowed addressing method. – Not allowed addressing method. |
Modicon Momentum
Data addressing method allowed depending on the module location in the architecture:
Addressing (addressing example) |
Momentum Bus + I/O-Bus |
||
Located I/O |
|||
Topological Addressing |
Topological (%lr.m.c) |
– |
|
IODDT (%CHr.m.c) |
– |
||
Flat or Modbus Addressing |
State RAM (%lx) |
X |
|
Located Memory (%MWx) |
X |
||
Unlocated I/O |
|||
Device DDT |
– |
||
X Allowed addressing method. – Not allowed addressing method. |