Features
System limitations:
At source time stamped events online change service is not available.
Internal PLC variables can not be timed stamped using at source time stamping solution.
No selection of transition edges on time stamped events in a BMX ERT 1604 T module (events are time stamped on rising and falling edges).
In a Modicon M340 local drop, the maximum number of BMX ERT 1604 T modules depends on the local drop CPU type, refer to Compatibility and Limitations topic for more details.
In a Quantum application, only 25 BMX ERT 1604 T modules are supported per application.
In an M580 application, the number of BMX ERT 1604 T modules per application is not limited.
NOTE: For M580 CPU with OS version ≤ 2.40, the number of BMX ERT 1604 T modules per application is limited to 25.A Modicon X80 Ethernet RIO drop supports up to 36 expert channels. A BMX ERT 1604 T module is counted as 4 expert channels.
Maximum of 9 x 140 ERT 854 10 modules in a S908 drop.
Maximum of 8 x 140 ERT 854 20 modules in a S908 drop.
Maximum of 2500 discrete I/Os per Quantum PLC.
Maximum of 144 discrete inputs per Modicon M340 PLC (local drop).
The CCOTF function is not supported by BMX ERT 1604 T modules.
Compatibility:
A Hot Standby system is compatible with applicative time stamping. For more details on Hot Standby system, refer to the Modicon Quantum Hot Standby System User Manual.
A Quantum Safety PLC is compatible with applicative time stamping. For more details, refer to the Modicon Quantum, Quantum Safety PLC, Safety Reference Manual.