Introduction
Observe the following guidelines when you install these Quantum and Modicon X80 modules in a Quantum EIO system:
140CRP31200 remote I/O head module (on the local rack)
remote I/O adapter module (on the remote I/O drop)
140CRA31200 module on a Quantum drop
140CRA31908 adapter module on a Quantum drop
BMXCRA312•0 module on a Modicon X80 drop
140NOC78000 distributed I/O head module (on the local rack)
140NOC78100 control network head module (on the local rack)
Grounding Considerations
DANGER | |
---|---|
Use fiber-optic cable to establish a communications link when it is not possible to master potential between distant grounds.
Installation
You can apply power to the Quantum EIO controller rack after the 140CRP31200 head module or adapter module is inserted:
Successful installation:
Initialization is finished.
Interconnections to other modules are validated (drop adapter module only).
Unsuccessful installation:
Initialization does not finish.
Interconnections to other modules are not validated (adapter modules only).
You can see the status of the installation on the LED display.