Code (hexadecimal)
|
Meaning
|
---|---|
16#1001
|
Abort by user
|
16#2001
|
An operation type that is not supported has been specified in the control block
|
16#2002
|
One or more control block parameters were modified while the MSTR element was active (this only applies to operations which require several cycles for completion). Control block parameters my only be modified in inactive MSTR components.
|
16#2003
|
Invalid value in the length field of the control block
|
16#2004
|
Invalid value in the offset field of the control block
|
16#2005
|
Invalid value in the length and offset fields of the control block
|
16#2006
|
Unauthorized data field on slave
|
16#2007
|
Invalid slot number in the configuration routing register
Example: 253 for 140 CRP 312 00 slot number
|
16#2008
|
Unauthorized network routing path on slave
|
16#200E
|
The control block is not assigned, or parts of the control block are located outside of the %MW (4x) range.
|
16#200F
|
The space allocated for the CIP response is too small.
|
16#3000
|
Generic Modbus exception response
|
16#3001
|
Slave does not support requested operation
|
16#3002
|
Non-existing slave registers were requested
|
16#3003
|
An unauthorized data value was requested
|
16#3005
|
Slave has accepted a lengthy program command
|
16#3006
|
Function cannot currently be carried out: lengthy command running
|
16#3007
|
Slave has rejected lengthy program command
|
16#4001
|
Inconsistent response by Modbus slave
|
16#F001
|
Module is resetting
|
16#F002
|
Component not fully initialized
|