Configuration Language Objects
(Original Document)
Description
The following table describes the process control language objects associated to 3-single-loop controllers.
Standard symbol
Type
Access
Meaning
Default Value
Address
CONFIG_0_B1
INT
R
Word grouping the various configuration bits of the process value
No object
%KWr.m.c.0
Filter
BOOL
R
Filtering function of the process value branch
Not configurable (0)
%KWr.m.c.0.0
Function Generator
BOOL
R
Function Generator for process value branch
Not configurable (0)
%KWr.m.c.0.1
Totaling
BOOL
R
Totaling Function for the process value branch
Missing (0)
%KWr.m.c.0.2
Square Root
BOOL
R
Root function of the process value branch
Square Root
%KWr.m.c.0.3
Alarms
BOOL
R
Alarm Function of the process value branch
Present
%KWr.m.c.0.4
PV_CLIP
BOOL
R
Lopping or non-lopping of process value
Missing (0)
%KWr.m.c.0.8
EXTRAPOL
BOOL
R
Extrapolation of function generator
Not configurable (0)
%KWr.m.c.0.9
PV_UNI_BIP
BOOL
R
Type of process value: unipolar/bipolar
Unipolar (0)
%KWr.m.c.0.10
PV_EXTERN
BOOL
R
Selection of Standard Process Value (0) vs. External Process Value (1)
Missing (0)
%KWr.m.c.0.11
VALID_C1
BOOL
R
Loop used (1) / not used (0)
Enabled (1)
%KWr.m.c.0.12
Totaling: Process value unit
BOOL
R
(bit 13 = 0, bit 14 = 0): phys/ms
(bit 13 = 1, bit 14 = 0): phys/s
1
%KWr.m.c.0.13
Totaling: Process value unit
BOOL
R
(bit 13 = 1, bit 14 = 0): phys/mn
(bit 13 = 1, bit 14 = 1): phys/ms
0
%KWr.m.c.0.14
CONFIG_1_B1
INT
R
Word grouping the various configuration bits of the setpoint
No object
%KWr.m.c.1
SP_SIMPLE
BOOL
R
Type of setpoint selected: simple.
Selected (1)
%KWr.m.c.1.0
SP_Selection
BOOL
R
Type of setpoint selected: selection.
Not configurable (0)
%KWr.m.c.1.1
SPEED_LIMITER
BOOL
R
Speed limiter on setpoint
Not selected (0)
%KWr.m.c.1.2
SP_SPP
BOOL
R
Type of setpoint selected: Programmer.
Not selected (0)
%KWr.m.c.1.3
LR/L
BOOL
R
Speed limiter either on local setpoint or in Remote/Local mode
Local remote (0)
%KWr.m.c.1.4
SEL_MIN
BOOL
R
Function selected if there is a selection setpoint
Not configurable (0)
%KWr.m.c.1.8
SEL_MAX
BOOL
R
Function selected if there is a selection setpoint
Not configurable (0)
%KWr.m.c.1.9
SEL_SWITCH
BOOL
R
Function selected if there is a selection setpoint
Not configurable (0)
%KWr.m.c.1.10
R/L_INIT
BOOL
R
Initial value of selected Remote/Local setpoint
Local (1)
%KWr.m.c.1.11
R1/R2_INIT
BOOL
R
Initial value of selected setpoint state
Not configurable
%KWr.m.c.1.12
SP_RATIO
BOOL
R
Type of setpoint selected: Ratio.
Not configurable (0)
%KWr.m.c.1.13
SP_LIMITER
BOOL
R
Setpoint Limiter (e.g. PARAM_SP)
not selected (0)
%KWr.m.c.1.14
SP_FOLW
BOOL
R
Tracking Setpoint (0)
No tracking
%KWr.m.c.1.15
CONFIG_2_B1
INT
R
Word grouping various configuration bits for loop controller and FF
No object
%KWr.m.c.2
PID
BOOL
R
PID function of loop controller branch
Present
%KWr.m.c.2.0
ONOFF2
BOOL
R
ON/OFF 2-states branch of loop controller
Missing (0)
%KWr.m.c.2.1
ONOFF3
BOOL
R
ON/OFF 3-states branch of loop controller
Missing (0)
%KWr.m.c.2.2
SPLRG/HOTCOLD
BOOL
R
OR Hot/Cold and Split Range presence bits
Not configurable (0)
%KWr.m.c.2.3
Split/Range
BOOL
R
Loop controller branch Split Range function.
Not configurable (0)
%KWr.m.c.2.4
Hot/Cold
BOOL
R
Hot/Cold function of loop controller branch
Not configurable (0)
%KWr.m.c.2.5
ALARMES_DEV
BOOL
R
Alarm function on diversion of loop controller branch
Present
%KWr.m.c.2.6
Feed Forward
BOOL
R
Presence of Feed Forward input
Not configurable (0)
%KWr.m.c.2.7
BUMP
BOOL
R
Bump Management when changing operating mode
With bumps (1)
%KWr.m.c.2.8
PV_DEV
BOOL
R
Type of derived action
On process value (0)
%KWr.m.c.2.9
MIX_PAR
BOOL
R
Mixed or parallel loop controller type
PID parallel series
%KWr.m.c.2.10
REV_DIR
BOOL
R
Type of loop controller action:
  • 1: opposite action, a positive shift (PV-SP) generates a rise of the output value
  • 0: direct action, a positive shift (PV-SP) generates a fall of the output value
PID opposite action (1)
%KWr.m.c.2.11
MANU/AUTO_INIT
BOOL
R
Initial value of loop controller operating mode
Manu (0)
%KWr.m.c.2.12
Lead Lag
BOOL
R
Lead Lag function of Feed Forward branch
Not configurable (0)
%KWr.m.c.2.13
FF_UNI_BIP
BOOL
R
Type of Feed Forward process value: unipolar/bipolar
Not configurable (0)
%KWr.m.c.2.14
IMC
BOOL
R
IMC function of loop controller branch
Missing (0)
%KWr.m.c.2.15
CONFIG_3_B1
INT
R
Word grouping the various output configuration bits
No object
%KWr.m.c.3
Servo
BOOL
R
Type of output selected: Servo.
Not selected
%KWr.m.c.3.0
Servo2
BOOL
R
Type of output selected: Servo.
Not configurable (0)
%KWr.m.c.3.1
Analog1
BOOL
R
Type of output selected: Analog.
Selected
%KWr.m.c.3.2
Analog2
BOOL
R
Type of output selected: Analog.
Not configurable (0)
%KWr.m.c.3.3
PWM1
BOOL
R
Type of output selected: PWM.
Not selected
%KWr.m.c.3.4
PWM2
BOOL
R
Type of output selected: PWM.
Not configurable (0)
%KWr.m.c.3.5
POT_REV1
BOOL
R
Servo copy direction
Direct (0)
%KWr.m.c.3.8
POT_REV2
BOOL
R
Servo copy direction
Not configurable (0)
%KWr.m.c.3.9
POT_VAL1_INIT
BOOL
R
Presence of Servo copy.
No (0)
%KWr.m.c.3.10
POT_VAL2_INIT
BOOL
R
Presence of (Reserved) Servo copy
Not configurable (0)
%KWr.m.c.3.11
ANALOG1_UNI_BIP
BOOL
R
Type of analog output: unipolar/bipolar
Unipolar
%KWr.m.c.3.12
ANALOG2_UNI_BIP
BOOL
R
Type of analog output: unipolar/bipolar
Not configurable (0)
%KWr.m.c.3.13
Loop name
INT
R
Loop Name.
Loop i with i [0.9]
%KWr.m.c.4
Loop Unit
INT
R
Loop Unit.
%KWr.m.c.8
IDEM BOUCLE 1 %KW0
INT
R
Loop 2 process value. Unused functions have their bit set at 0.
%KWr.m.c.11
IDEM BOUCLE 1 %KW1
INT
R
Loop 2 setpoint.
%KWr.m.c.12
IDEM BOUCLE 1 %KW2
INT
R
Loop 2 loop controller and FF.
%KWr.m.c.13
IDEM BOUCLE 1 %KW3
INT
R
Loop 2 output.
%KWr.m.c.14
IDEM BOUCLE 1 %KW4
INT
R
Loop Name.
Loop i with i [0.9]
%KWr.m.c.15
IDEM BOUCLE 1 %KW8
INT
R
Loop Unit.
%KWr.m.c.19
IDEM BOUCLE 1 %KW0
INT
R
Loop 3 process value. Unused functions have their bit set at 0.
%KWr.m.c.22
IDEM BOUCLE 1 %KW1
INT
R
Loop 3 setpoint.
%KWr.m.c.23
IDEM BOUCLE 1 %KW2
INT
R
Loop 3 loop controller and FF.
%KWr.m.c.24
IDEM BOUCLE 1 %KW3
INT
R
Loop 3 output.
%KWr.m.c.25
IDEM BOUCLE 1 %KW4
INT
R
Loop Name.
Loop i with i [0.9]
%KWr.m.c.26
IDEM BOUCLE 1 %KW8
INT
R
Loop Unit.
%KWr.m.c.30
Trigger mode of loop 1
BOOL
R
Trigger mode:
bit 0 = 0: automatic
0
%KWr.m.c.34.0
Trigger mode of loop 2
BOOL
R
Trigger mode:
bit 0 = 0: automatic
0
%KWr.m.c.35.0
Trigger mode of loop 3
BOOL
R
Trigger mode:
bit 0 = 0: automatic
0
%KWr.m.c.36.0