Configuration Language Objects
(Original Document)
At a Glance
The following table lists all language objects associated with the process loop. These objects are not included in the IODDTs. They may however be displayed with the project program.
Description
Standard symbol
Type
Access
Meaning
Default Value
Address
CONFIG_0
INT
R
This word gathers all different process value configuration bits.
No object
%KWr.m.c.0
Filter
BOOL
R
Filtering function of the process value branch
Missing (0)
%KWr.m.c.0.0
Function Generator
BOOL
R
Function Generator for process value branch
Missing (0)
%KWr.m.c.0.1
Totaling
BOOL
R
Totaling Function for the process value branch
Missing (0)
%KWr.m.c.0.2
Square Root
BOOL
R
Square root function of the process value branch
Missing (0)
%KWr.m.c.0.3
Alarms
BOOL
R
Alarm Function of the process value branch
Present
%KWr.m.c.0.4
PV_CLIP
BOOL
R
Lopping or non-lopping of measurement.
Missing (0)
%KWr.m.c.0.8
EXTRAPOL
BOOL
R
Extrapolation of function generator
No (0)
%KWr.m.c.0.9
PV_UNI_BIP
BOOL
R
Type of process value: unipolar/bipolar.
Unipolar (0)
%KWr.m.c.0.10
PV_EXTERN
BOOL
R
Selection of Standard Process Value (0) vs. External Process Value (1).
Missing (0)
%KWr.m.c.0.11
Totaling
BOOL
R
(bit 13 = 0, bit 14 = 0): phys/ms
(bit 13 = 1, bit 14 = 0): phys/s
1
%KWr.m.c.0.13
Totaling
BOOL
R
(bit 13 = 1, bit 14 = 0): phys/ms
(bit 13 = 1, bit 14 = 1): phys/s
0
%KWr.m.c.0.14
No object
INT
R
Word grouping the various configuration bits of the setpoint
No object
%KWr.m.c.1
SP_SIMPLE
BOOL
R
Type of setpoint selected: simple.
Selected (1)
%KWr.m.c.1.0
SP_Selection
BOOL
R
Type of setpoint: selection.
Not selected (0)
%KWr.m.c.1.1
SPEED_LIMITER
BOOL
R
Speed limiter on setpoint
Not selected (0)
%KWr.m.c.1.2
SP_SPP
BOOL
R
Type of setpoint selected: programmer.
not selected (0)
%KWr.m.c.1.3
LR/L
BOOL
R
Speed limiter either on local setpoint, or in Remote/Local mode.
Local remote (0)
%KWr.m.c.1.4
SEL_MIN
BOOL
R
Function selected if there is a selection setpoint
Missing (0)
%KWr.m.c.1.8
SEL_MAX
BOOL
R
Function selected if there is a selection setpoint
Missing (0)
%KWr.m.c.1.9
SEL_SWITCH
BOOL
R
Function selected if there is a selection setpoint
Present on selection
%KWr.m.c.1.10
R/L_INIT
BOOL
R
Initial value of selected Remote/Local setpoint
Local (1)
%KWr.m.c.1.11
R1/R2_INIT
BOOL
R
Initial value of selected setpoint state
R1 (0)
%KWr.m.c.1.12
SP_RATIO
BOOL
R
Type of setpoint selected: ratio.
Not selected (0)
%KWr.m.c.1.13
SP_LIMITER
BOOL
R
Setpoint limiter (e.g.: Param_SP).
Not present
%KWr.m.c.1.14
SP_FOLW
BOOL
R
Tracking setpoint.
Non tracking setpoint (0)
%KWr.m.c.1.15
CONFIG_2
INT
R
Word grouping various configuration bits for loop controller and FF
No object
%KWr.m.c.2
PID
BOOL
R
PID function of loop controller branch
Present
%KWr.m.c.2.0
ONOFF2
BOOL
R
ON/OFF 2-states branch of loop controller
Missing (0)
%KWr.m.c.2.1
ONOFF3
BOOL
R
ON/OFF 3-states branch of loop controller
Missing (0)
%KWr.m.c.2.2
SPLRG/HOTCOLD
BOOL
R
OR Hot/Cold and Split Range presence bits
No object
%KWr.m.c.2.3
Split Range
BOOL
R
Loop controller branch Split Range function.
Missing (0)
%KWr.m.c.2.4
Hot/Cold
BOOL
R
Hot/Cold function of loop controller branch
Not selected
%KWr.m.c.2.5
ALARMES_DEV
BOOL
R
Alarm function on diversion of loop controller branch
Present
%KWr.m.c.2.6
Feed Forward
BOOL
R
Presence of Feed Forward input
Missing (0)
%KWr.m.c.2.7
BUMP
BOOL
R
Bump Management when changing operating mode
With bumps (1)
%KWr.m.c.2.8
PV_DEV
BOOL
R
Type of derived action
On process value (0)
%KWr.m.c.2.9
MIX_PAR
BOOL
R
Mixed or parallel loop controller type
PID parallel series
%KWr.m.c.2.10
REV_DIR
BOOL
R
Type of loop controller action:
  • 1: opposite action, a positive shift (PV-SP) generates a rise of the output value
  • 0: direct action, a positive shift (PV-SP) generates a fall of the output value
PID opposite action (1)
%KWr.m.c.2.11
MANU/AUTO_INIT
BOOL
R
Initial value of loop controller operating mode
Manu (0)
%KWr.m.c.2.12
Lead Lag
BOOL
R
Lead Lag function of Feed Forward branch
Missing (0)
%KWr.m.c.2.13
FF_UNI_BIP
BOOL
R
Type of Feed Forward process value: unipolar/bipolar.
unipolar
%KWr.m.c.2.14
IMC
BOOL
R
IMC function of loop controller branch
Missing (0)
%KWr.m.c.2.15
CONFIG_3
NIT
R
Word grouping the various output configuration bits
No object
%KWr.m.c.3
Servo
BOOL
R
Type of output selected: Servo.
Selected
%KWr.m.c.3.0
Servo2
BOOL
R
Type of output selected: Servo.
Selected
%KWr.m.c.3.1
Analog1
BOOL
R
Type of output selected: Analog.
Selected
%KWr.m.c.3.2
Analog2
BOOL
R
Type of output selected: Analog.
Selected
%KWr.m.c.3.3
PWM1
BOOL
R
Type of output selected: PWM.
Selected
%KWr.m.c.3.4
PWM2
BOOL
R
Type of output selected: PWM.
Selected
%KWr.m.c.3.5
POT_REV1
BOOL
R
Servo copy direction
Direct (0)
%KWr.m.c.3.8
POT_REV2
BOOL
R
Servo copy direction
Direct (0)
%KWr.m.c.3.9
POT_VAL1_INIT
BOOL
R
Presence of Servo copy.
No (0)
%KWr.m.c.3.10
POT_VAL2_INIT
BOOL
R
Presence of (Reserved) Servo copy
Yes (1)
%KWr.m.c.3.11
ANALOG1_UNI_BIP
BOOL
R
Type of analog output: unipolar/bipolar.
Unipolar
%KWr.m.c.3.12
ANALOG2_UNI_BIP
BOOL
R
Type of analog output: unipolar/bipolar.
Unipolar (0)
%KWr.m.c.3.13
Loop name
INT
R
Loop Name.
Loop i with i [0.9]
%KWr.m.c.4
Loop Unit
INT
R
Loop Unit.
%KWr.m.c.8
Trigger mode
BOOL
R
Trigger mode:
bit 0 = 0: automatic
0
%KWr.m.c.11.0