Accessing the Wizard

Step

Action

1

Create a new application in Control Expert selecting a CPU with enough memory and the I/O access capabilities needed (e.g. Modicon M340).

2

Launch the conversion wizard in Control Expert via Tools > Convert Partially.

3

A file selection dialog is displayed, offering a choice of exported legacy application files (e.g FEF files for PL7, ASC files for Concept etc.).

4

Select a file and confirm with Open.

Result: Depending on the kind of file selected the respective converter (PL7, Concept, LL984) becomes active and analyzes the content of the selected file.

The result of the analysis is displayed in the 3 tabs of the conversion wizard.

Exported Files

Software

Extension

Exported

PL7

*.fef

complete application

Concept

*.asc

complete application

Concept

*.sec

user-defined subset of sections

Concept

*.txt

user-defined subset of variables

Concept

*.ccf

configuration export to extract communication definitions

ProWORX32

*.pwx

complete application

MODSOFT

*.cfg

complete application

Control Expert

*.xpg

tasks (without configuration)