At a Glance

Automatic and manual accesses are carried out between the Schneider BMX RMS ••••• memory card and Control Expert or the PLC to:

  • restore a project in the PLC

  • save the PLC project on the memory card

  • compare the PLC project and the memory card project

Restore Function

The restore function is carried out as follows:

  • Automatically:

    • after a power cycle

    • on a warm start

    • on a cold start

  • Manually, using the Control Expert command PLC > Project Backup... > Backup Restore.

NOTE:
  • When you insert the memory card in run or stop mode, power cycle to restore the project on the PLC.

  • If the application contained in the memory card includes the RUN AUTO option, then the PLC will automatically restart in RUN mode with this application as soon as the inserted memory card content is restored to the PLC.

Save Function

The save function is carried out as follows:

  • Automatically, after:

    • a download, if the memory card is present and not write-protected

    • online modification, if the memory card is present and not write-protected

    • detection of a system bit %S66 rising edge

  • Manually, using the command PLC > Project Backup... > Backup Save .

NOTE: If you remove the memory card when the backup is in progress, the program on the memory card is lost. With system bit %S65 you can disable processor access to the memory card.

If the memory card is not present or write-protected, the download in Processor memory is allowed but the online modification is not allowed.

Compare Function

You can compare your project with the one contained on the memory card. To do so, use the command PLC > Project Backup... > Compare .

Memory Card State and Diagnostic

Control Expert and the PLC front panel display the status of the memory card:

Display on

Icon/LED State

Description

Status bar at bottom of Control Expert

Project on memory card is different from PLC project.

Memory card is not present on the PLC or is inoperable.

no icon

Project in memory card is equivalent to PLC project.

LED on bottom of memory card slot

On

Access to the memory card is enabled.

Flashing

Activity between the memory card and the PLC.

Off

Access to the memory card is disabled. You can remove the memory card.

CARDERR LED on PLC front panel

On

Memory card is missing or memory card is not detected, or project on memory card is different from PLC project.

Off

Memory card is detected, and project in memory card is equivalent to PLC project.