Forced Variable Behavior

The behavior of forced variables has been changed between Modsoft/NxT/Concept and Control Expert.

With Modsoft/NxT/Concept you cannot force variables (0x, 1X) with the Quantum CPU memory protect switch in the ON position.

With Control Expert you can force variables (%M, %I, %Q) with the Quantum CPU memory protect switch in the ON position.

When using a basic Quantum CPU, if the memory protect switch is in the OFF position, some variables are forced and the application is saved in flash memory:

  • with Modsoft/NxT/Concept, forced variables keep their state after a cold start,

  • with Control Expert, forced variables lose their state after a cold start.

Warning Message when Forcing Variables

A warning message will display in Control Expert each time that variables are forced on the following Quantum PLCs:

  • 140 CPU 311 10

  • 140 CPU 434 12A/U

  • 140 CPU 534 14A/U

This warning message includes a "Do not warn me again" option so that, when checked, the message will not be redisplayed during the current Control Expert session. Starting a new session of Control Expert means that the option must be checked once more in order to no longer see it when forcing a variable.