At a Glance
The inputs
associated with a task can be deactivated using the system word %SW8.
The outputs
associated with a task can be deactivated using the system word %SW9.
Precautions
WARNING |
---|
| UNEXPECTED APPLICATION BEHAVIOR - OUTPUTS DEACTIVATION Before deactivating an Output, take into account its deactivation
mode (fallback or maintain). Failure to follow these instructions can result in death, serious injury, or equipment damage. |
CAUTION |
---|
| UNEXPECTED APPLICATION BEHAVIOR Before setting the %SW9 value
to 1, ensure that the output behavior will remain appropriate: On Premium/Atrium: Module outputs located on the X Bus automatically switch
to the configured mode (fallback or maintain). On the Fipio bus, certain
devices do not manage fallback mode; then only maintain mode is possible. On Quantum: All outputs, as well as the local or remote rack (RIO)
are maintained in the state that preceded the switch to 1 of the %SW9 bit corresponding to the task. The Distributed Inputs/Outputs (DIO) are not assigned
by the system word %SW9. Failure to follow these instructions can result in injury or equipment damage. |