Overview
Time stamping can be applied to various architectures that include at least a SCADA, an OFS, and a PLC (Modicon M580, M340, or Quantum with Modicon X80 Ethernet I/O drop).
System Time Stamping with a Modicon M580 CPU
The following table presents the devices combination required in a system time stamping architecture with a Modicon M580 CPU in the local drop:
SCADA |
OPC DA Server |
OPC UA Server |
PLC (Local Drop) |
Ethernet Remote I/O Drop |
||||
---|---|---|---|---|---|---|---|---|
Family |
Time Stamping Source |
Time Synchronization |
Family |
Time Stamping Source |
Time Synchronization |
|||
AVEVA Plant SCADA or 3rd party SCADA (1.) |
OFS + 1 or more I/O servers |
BME NUA 0200 2 modules max per rack |
Modicon M580 |
BME P58 ••••4 |
NTP server |
Modicon X80 (2.) |
BM• CRA 312 10 |
NTP server (3.) |
BMX ERT 1604 T |
DCF77 or IRIG-B 004/5/6/7 |
BMX ERT 1604 T |
DCF77 or IRIG-B 004/5/6/7 |
|||||
Mix of both possible sources:
|
Each source has its time reference:
|
Mix of both possible sources:
|
Each source has its time reference:
|
|||||
N.A. Not Applicable 1. Redundant SCADA configuration is compatible with system time stamping. 2. A time stamping architecture may contain several Ethernet remote I/O drops with time stamping sources. 3. A single NTP server can provide time reference to many BM• CRA 312 10 modules and a BME P58 •••• CPU. 4 The SAFE task does not suppot time stamping of internal variables by the BME P58 ••••S CPU |
System Time Stamping with a Modicon M340 CPU
The following table presents the devices combination required in a system time stamping architecture with a Modicon M340 CPU in the local drop:
SCADA |
OPC DA Server |
PLC (Local Drop) |
Ethernet Remote I/O Drop |
||||
---|---|---|---|---|---|---|---|
Family |
Time Stamping Source |
Time Synchronization |
Family |
Time Stamping Source |
Time Synchronization |
||
AVEVA Plant SCADA or 3rd party SCADA (1.) |
OFS + 1 or more I/O servers |
Modicon M340 |
BMX ERT 1604 T |
DCF77 or IRIG-B 004/5/6/7 |
N.A. |
N.A. |
N.A. |
N.A. Not Applicable 1. Redundant SCADA configuration is compatible with system time stamping. |