Overview

Time stamping can be applied to various architectures that include at least a SCADA, an OFS, and a PLC (Modicon M580, M340, or Quantum with Modicon X80 Ethernet I/O drop).

System Time Stamping with a Modicon M580 CPU

The following table presents the devices combination required in a system time stamping architecture with a Modicon M580 CPU in the local drop:

SCADA

OPC DA Server

OPC UA Server

PLC (Local Drop)

Ethernet Remote I/O Drop

Family

Time Stamping Source

Time Synchronization

Family

Time Stamping Source

Time Synchronization

AVEVA Plant SCADA or 3rd party SCADA (1.)

OFS

+

1 or more I/O servers

BME NUA 0200

2 modules max per rack

Modicon M580

BME P58 ••••4

NTP server

Modicon X80 (2.)

BM• CRA 312 10

NTP server (3.)

BMX ERT 1604 T

DCF77 or IRIG-B 004/5/6/7

BMX ERT 1604 T

DCF77 or IRIG-B 004/5/6/7

Mix of both possible sources:

  • BME P58 ••••4

  • BMX ERT 1604 T

Each source has its time reference:

  • NTP server for BME P58 ••••

  • DCF77 or IRIG-B 004/5/6/7 for BMX ERT 1604 T

Mix of both possible sources:

  • BM• CRA 312 10

  • BMX ERT 1604 T

Each source has its time reference:

  • NTP server (3.) for BM• CRA 312 10

  • DCF77 or IRIG-B 004/5/6/7 for BMX ERT 1604 T

N.A. Not Applicable

1. Redundant SCADA configuration is compatible with system time stamping.

2. A time stamping architecture may contain several Ethernet remote I/O drops with time stamping sources.

3. A single NTP server can provide time reference to many BM• CRA 312 10 modules and a BME P58 •••• CPU.

4 The SAFE task does not suppot time stamping of internal variables by the BME P58 ••••S CPU

System Time Stamping with a Modicon M340 CPU

The following table presents the devices combination required in a system time stamping architecture with a Modicon M340 CPU in the local drop:

SCADA

OPC DA

Server

PLC (Local Drop)

Ethernet Remote I/O Drop

Family

Time Stamping Source

Time Synchronization

Family

Time Stamping Source

Time Synchronization

AVEVA Plant SCADA or 3rd party SCADA (1.)

OFS

+

1 or more I/O servers

Modicon M340

BMX ERT 1604 T

DCF77 or IRIG-B 004/5/6/7

N.A.

N.A.

N.A.

N.A. Not Applicable

1. Redundant SCADA configuration is compatible with system time stamping.