Specifications
Original instructions
General Specification
General Specification
Bus Current required
750 mA
Power Dissipation (Typical)
3.8 W
I/O Type
Quantum
Modules/Drop
14 max.
28 max. with Backplane expander (XBE)
Words/Drop
64 IN / 64 OUT
Holdup Time
Software configurable
NOTE: You can specify a monitoring time of 3 - 65 535 in this text box. With communication interruptions with the remote processor, the output modules will maintain their last operating condition during that time. Once the monitoring time has expired, the output modules will reset to their default timeout status. The monitoring time does not influence input modules. The CPU will immediately set the input values to zero.
Connection / Transmission
Connection / Transmission
Coax Termination
Internal 75 ohms
Coax Shield
Capacitor to ground
Data Transfer Rate
1.544 Mb
Dynamic Range
35 dB
External Connections
Two "F" type female connector with a right angle adapter
Diagnostics
Diagnostics
Power Up
Runtime
Dual Port Memory Check
LAN Controller Check
Executive Checksum
RAM Address/Data