Table elements
|
Most significant byte
|
Least significant byte
|
---|---|---|
Management_Param[0]
|
Exchange number.
|
-
|
Management_Param[1]
|
Operation report.
|
Communication report.
|
Management_Param[2]
|
Timeout: if the exchange is not completed in a time under the Timeout value, the function is cancelled (the exchange is stopped). The Timeout value is a multiple of 100ms, for example: 20 means 20x100ms, or 2 seconds.
|
|
Management_Param[3]
|
Length: number of bytes received in the reception table. This length shows the exact size of the data received from the Lexium controller.
|
|
Management_Param[4]
|
-
|
Activity bit.
|
The words Management_Param[5] to Management_Param[13] are reserved.
|
Description
|
Operation report value
|
Communication report value
|
---|---|---|
The address format is incorrect.
|
16#00
|
16#03
|
The type of object is different from 'P' or 'MT'.
|
16#00
|
16#06
|
The management parameters are less than 14 words long.
|
16#00
|
16#05
|
The frame received from the Fipio card does not contain any data.
|
16#03
|
16#00
|
The frame received from the Fipio card is of an incorrect length.
|
||
The frame received from the Fipio card contains the response code FD.
(1)
|
16#01
|
16#00
|
The length of the word zone is insufficient to save data.
(2)
|
16#00
|
16#09
|
Incorrect response from Lexium.
|
16#32
|
16#00
|
Memory capacity of Fipio card on Lexium exceeded.
|
16#33
|
16#00
|
Key:
|
||
(1)
|
For example, when another request is being processed.
|
|
(2)
|
In this case, the minimum number of bytes required to save the data is specified in the word %MWg+3.
|