Schneider Automation offers a range of 1 mm diameter plastic fiber optic cables for connecting the different components of the SERCOS network (TSX CSY 84/164 modules and variable speed controllers). Each cable is equipped at each end with an SMA type connector.
The table below provides the reference and length of each cable.
References
|
Lengths
|
990 MCO 00001
|
0.3 meters
|
990 MCO 00003
|
0.9 meters
|
990 MCO 00005
|
1.5 meters
|
990 MCO 00015
|
4.5 meters
|
990 MCO 00055
|
16.5 meters
|
990 MCO 00075
|
22.5 meters
|
990 MCO 000125
|
37.5 meters
|
When installing fiber optic cables, it is necessary to comply with the following recommendations:
NOTE: Recommendations concerning the curve radius of the cables.
For this type of cable, the minimum curve radius must be greater than 25 mm.
Failure to observe this may result in damage to the cables.
NOTE: Recommendation concerning the tension applied to the cables on installation.
The maximum tension applied to the cables on installation must not exceed 6 Kg.
Failure to observe this may result in damage to the cables.
Maximum permitted temperature: -40°C+80°C.