Details of the implicit exchange objects of the IODDT of type T_CCY_GROUP1_2_3
(Original Document)
At a Glance
The IODDT of type T_CCY_GROUP1_2_3 has implicit exchange objects, which are described below. This type of IODDT applies to the TSX CCY 1128 module for channels 1, 2 and 3.
Example of declaring a variable: IODDT_VAR1 of type T_CCY_GROUP1_2_3
Generally speaking, the meaning of the bits is given for state 1 of this bit. In specific cases, the two states of the bit are explained.
List of implicit exchange %IW input objects
The table below shows the implicit exchange %IW input objects of the IODDT of type T_CCY_GROUP1_2_3 which applies to channel 0 of the TSX CCY 1128 module.
Standard symbol
Type
Access
Meaning
Number
GROUP0_TRACKS
INT
R
bit 0 to bit 7: state of group 0 tracks
%IWr.m.0.0
List of implicit exchange %QW output objects
The table below shows the implicit exchange %QW output objects of the IODDT of type T_CCY_GROUP1_2_3 which applies to channel 0 of the TSX CCY 1128 module.
Standard symbol
Type
Access
Meaning
Number
ENAB_GROUP_BITS
INT
RW
bit 0 to bit 7 = 1: validation of cams by track from 0 to 7, of group
%QWr.m.0.0
GROUP_AND_BITS
INT
RW
bit 0 to bit 7 = 1: assignment of tracks to group outputs
%QWr.m.0.1
GROUP_OR_BITS
INT
RW
bit 0 to bit 7 = 1: forcing group outputs (to 1)
%QWr.m.0.2