Parameter designation
|
Symbols
|
Values
|
Units
|
||
|---|---|---|---|---|---|
|
Nominal values
|
Voltage
|
Un
|
24
|
V
|
|
|
Current
|
In
|
500
|
mA
|
||
|
Thresholds
|
Voltage
|
U1
|
19...30
|
V
|
|
|
Utime (1)
|
34
|
V
|
|||
|
Maximum current per output for U= 30 V or 34 V
|
I1
|
600
|
mA
|
||
|
Maximum current
|
per connector
|
I2
|
< 6
|
A
|
|
|
per module
|
I3
|
< 12
|
A
|
||
|
Maximum power for lamp with tungsten filament
|
P1
|
10
|
W
|
||
|
Maximum switching frequency on inductive load
|
F
|
<0.6/LI
|
Hz
|
||
|
Electro unload time
|
T
|
< L/R
|
s
|
||
|
Pre-actuator voltage check threshold
|
OK
|
Uok
|
> 18
|
V
|
|
|
Fault
|
Udef
|
< 14
|
V
|
||
|
Compatibility with direct current inputs
|
All direct current inputs with positive logic, and an input resistance of < at 15 kOhms
|
||||
|
Protection against overloads and short-circuits
|
Using current limiter and thermal circuit breaker (0.7A<Id<2A)
|
||||
|
Protection against overvoltage of the outputs
|
Using a Zener (breakdown) diode between the outputs and the +24V
|
||||
|
Protection against polarity inversions
|
Using a reverse diode on the supply
|
||||
|
Dielectric rigidity with the ground connection
|
1500 V eff 50/60 Hz per mn
|
||||
|
Compliance with IEC 1131-2
|
Yes
|
||||