Maximum frequency of counting:
absolute SSI encoder: transmission CLK frequency
incremental encoder
|
200 kHz
500 kHz x 1
250 kHz x 4
|
||
Current used on internal 5 V (ventilator in operation)
|
Module
|
Typical
|
Max.
|
CAY 2•
CAY 4•/33
|
1.1 A
1.5 A
|
1.4 A
1.8 A
|
|
Current used on the 24V sensor/
pre-sensor, outputs OFF
|
CAY 2•
CAY 4•/33
|
15 mA
30 mA
|
18 mA
36 mA
|
Current consumed by the module on the 10/30 V encoder at 24V (1)
|
CAY 2•
CAY 4•/33
|
11 mA
22 mA
|
20 mA
40 mA
|
Power dissipated in the module
|
CAY 2•
CAY 4•/33
|
7.2 W (2)
10 W (2)
|
11.5 W (3)
17 W (3)
|
Insulation resistance
|
> 10 MΩ under 500 VDC
|
||
Dielectric rigidity with ground connection or 0 V logical PLC
|
1000 Veff 50/60 Hz per min
|
||
Operating temperature
|
0 to 60 °C
|
||
Storage temperature
|
-25 °C to 70 °C
|
||
Hygrometry (without condensation)
|
5% to 95%
|
||
Operating altitude
|
< 2000 m
|