Parameter
|
Indication
|
---|---|
Following error 1
|
Moving part stopped by critical deviation between calculated position (setpoint) and measured position of moving part.
By default Following error 1 = (LMAX – LMIN)/100
Critical error: 0 to (SL_MAX - SL_MIN)/4
Following error 1 = 0: no control
|
Following error 2
|
Deviation between calculated position (setpoint) and measured position of moving part, which only causes a fault to be signalled.
By default Following error 2 = (LMAX – LMIN)/100
Preventive error: 0 to (SL_MAX - SL_MIN)/4
Following error 2 = 0: no control
|
Parameter
|
Indication
|
---|---|
Recalibration position
|
Value that measured position must have during a recalibration event.
By default Recalibration position = (LMAX - LMIN)/4 + LMIN (if it is a configured recalibration function)
Limits: SL_MIN + TW to SL_MAX - TW, where TW = tolerance for target window control
Recalibration position = 0 : no control
|
Recalibration deviation
|
Maximum gap between recalibration position and measured position of moving part during a recalibration event. A larger deviation will trigger a recalibration.
By default Recalibration deviation = (LMAX - LMIN)/100 + LMIN (if it is a configured recalibration function)
Static error: 0 to DMAX1/2
Recalibration deviation = 0: no control
|
Parameter
|
Indication
|
---|---|
Overspeed
|
Fault threshold for measured overspeed, expressed as a % of VMAX.
By default Overspeed = 10%
Overspeed: 0 to 20%
Overspeed = 0: no control
|
Parameter
|
Indication
|
---|---|
VLIM
|
Detection threshold for movement control.
Unit: mV
Limits: 0 to 9000
VLIM = 0: no control
|