Specifications
Original instructions
Overview
This section contains specifications for the 170 ADM 350 15 I/O base.
NOTE: In order for the 170 ADM 350 15 module to comply with the Directives 73/23/EEC (LV) and 89/336/EEC (EMC) and the IEC standards, EN 61131-2:2003 and EN 55011, the module must be used with a Telemecanique power supply, model numbers ABL7 RE2403, ABL RE2405, or ABL RE2410.
General Specifications
Module type
16 discrete inputs in 1 group
16 discrete outputs in 2 groups (8 pts/group)
Supply voltage
24 VDC
Supply voltage range
20-30 VDC
Supply current consumption
max. 250 mA at 24 VDC
Power dissipation
6 W + ( ( # of input points on x .144 W) + (# of output points on x .25 W) )
I/O map
1 input word
1 output word
Isolation
Input to input
none
Output to output
none
Input to output group
500 VAC for 1 minute
I/O Points to Communication Interface
500 VAC for 1 minute
Module power to logic
none
Module power to I/O points
500 VAC for 1 minute
Fuses
Internal
none
External: module power
1 A slow-blow (Bussmann GDC-1A or equivalent)
External: input power
1 A slow-blow (Bussmann GDC-1A or equivalent)
External: output power
According to the supply of the connected actuators–not to exceed 6.3 A fast-blow/ group
EMC
Immunity
IEC 1131-2
Surge on auxiliary power supply 500V
Emissions
EN 50081-2
Agency approvals
UL, CSA, CE, FM Class 1, Div. 2 pending
Physical Dimensions
Width
125 mm (4.9 in)
Depth (with no adapter)
40 mm (1.54 in)
Length
141.5 mm (5.5 in) no or one busbar
159.5mm (6.3in) two busbars
171.5 mm (6.75in) three busbars
Weight
200 g (0.44 lb)
Discrete Inputs
Number of points
16
Number of groups
1
Points per group
16
Signal type
True Low
IEC 1131 type
1 (See Appendix Input Voltage and Current Thresholds for definitions of IEC input types.)
ON voltage
0 ... 5 VDC
OFF voltage
15 ... 30 VDC
Input current
2.0 mA minimum ON
0.5 mA maximum OFF
Input voltage range
0 ... +30 VDC
Input resistance
4 kOhm
Response time
2.2 ms OFF to ON
3.3 ms ON to OFF
Discrete Outputs
Output type
Solid state switch (sinking)
Output supply voltage
24 VDC
Output supply voltage range
20-30 VDC
Number of points
16
Number of groups
1
Current capacity
0.5 A/point maximum
5 A/module
Signal type
True Low
Leakage current (output out)
< 1 mA @ 24 VDC
Surge (inrush) current
1 A for 1 ms Current limited
On state voltage drop
< 0.5 VDC @ 0.5 A
Fault sensing
(See Note Below)
Outputs are electronically safeguarded to assist in short circuit and overload protection
Fault indication
1 red LED/point (row 3) ON when short current/ overload occurs
Error reporting
none
Response time
(resistive load / 0.5 A)
< 1 ms OFF to ON
< 1 ms ON to OFF
Maximum switching cycles
1000/h for 0.5 A inductive load
100/s for 0.5 A resistive load
8/s for 1.2 W Tungsten load
Loads
Inductive
500 mH @ 0.5 Hz
Capacitance
50 microfarads
Tungsten Load
12 W
Input Voltage Surge
45 Volt for 10 ms
56 Volt for 1.3 mS decaying pulse
NOTE: Discrete 24 VDC outputs incorporate thermal shutdown and overload protection. The output current of a shortened output is limited to a nondestructive value. The short circuit heats the output driver and the output will switch off. The output will switch on again if the driver leaves the over temperature condition. If the short circuit still exists, the driver will reach the over temperature condition again and will switch off again.