Type
|
Part Number
|
---|---|
Screw-in
|
170 XTS 001 00
|
Spring-clip
|
170 XTS 002 00
|
Type
|
Part Number
|
---|---|
Screw-in
|
170 XTS 006 01
|
Spring-clip
|
170 XTS 007 01
|
![]() |
POTENTIAL FOR SHORT CIRCUITS AND/OR POWER-UP SPIKES
Provide external fuses on the operating voltage to protect the module. Appropriate fuse values are shown in the wiring illustration. An unprotected module may be subject to short circuits and/or power-up spikes.
Failure to follow these instructions can result in injury or equipment damage.
|
Row
|
Terminal
|
Function
|
---|---|---|
1
|
Fuse 1, Fuse 2
|
Output fuses
|
2
|
1, 3, 5, 7
|
Outputs for group 1
|
9,11 ,13, 15
|
Outputs for group 2
|
|
17
|
Neutral for outputs (1N)
|
|
18
|
Line for outputs (1L1)
|
|
3
|
1 ... 16
|
Neutral for individual outputs (1N)
|
17
|
Neutral 120 VAC for module (N)
|
|
18
|
Line 120 VAC for module (L1)
|
|
4
|
1 ... 18
|
Protective earth (PE)
|