Type
|
Part Number
|
---|---|
Screw-in
|
170 XTS 001 00
|
Spring-clip
|
170 XTS 002 00
|
Type
|
Number of Rows
|
Part Number
|
---|---|---|
Screw-in
|
1 - row
|
170 XTS 006 01
|
2 - row
|
170 XTS 005 01
|
|
3 - row
|
170 XTS 004 01
|
|
Spring-clip
|
1 - row
|
170 XTS 007 01
|
2 - row
|
170 XTS 008 01
|
|
3 - row
|
170 XTS 003 01
|
![]() |
POTENTIAL FOR SHORT CIRCUITS AND/OR POWER-UP SPIKES
Provide external fuses on the operating voltage to protect the module. Appropriate fuse values are shown in the wiring illustration. An unprotected module may be subject to short circuits and/or power-up spikes.
Failure to follow these instructions can result in injury or equipment damage.
|
Row
|
Terminal
|
Function
|
---|---|---|
1
|
1...16
|
Inputs
|
17
|
Return (M-)
|
|
18
|
+ 24 VDC Operating voltage (L+)
|
|
2
|
1 ... 8
|
Outputs for group 1
|
9 ... 16
|
Outputs for group 2
|
|
17/18
|
+ 24 VDC for output group 1 (1L+) and group 2 (2L+)
|
|
3
|
1 ... 16
|
Return for outputs
|
17/18
|
Return (M-)
|
|
4
|
1 ... 18
|
Input voltage for inputs I1 ... I16 or PE
|
5
|
1 ... 18
|
Return (M-)
|
6
|
1 ... 18
|
Protective earth (PE)
|