Field Wiring Guidelines
Original instructions
Overview
Inputs are field wired to row 1 of the base. This section contains wiring guidelines and precautions.
Terminal Connector
To connect field devices to the I/O base, you need a field wiring terminal connector. Schneider Electric sells terminal connectors in sets of three.
Type
Part Number
Screw-in
170 XTS 001 00
Spring-clip
170 XTS 002 00
Mapping Terminal Blocks
CAUTION
POTENTIAL FOR SHORT CIRCUITS AND/OR POWER-UP SPIKES
Provide external fuses on the operating voltage to protect the module. Appropriate fuse values are shown in the wiring illustration. An unprotected module may be subject to short circuits and/or power-up spikes.
Failure to follow these instructions can result in injury or equipment damage.
The following table shows mapping terminal blocks.
Row
Terminal
Function
1
1...16
Inputs
17
Neutral - 120 VAC for module (N)
18
Line - 120 VAC for module (L1)
2
1 ... 8
Input group 1 - line (1L1)
9 ... 16
Input group 2 - line (2L1)
17
Line for inputs group 1 (1L1)
18
Line for inputs group 2 (2L1)
3
1 ... 8
Input group 1 - neutral (1N)
9 ... 16
Input group 2 - neutral (2N)
17
Neutral for inputs group 1 (1N)
18
Neutral for inputs group 2 (2N1)