Field Wiring Guidelines
Original instructions
Overview
This section contains wiring guidelines and precautions.
Terminal Connector
To connect field devices to the I/O base, you need a field wiring terminal connector. Schneider Electric sells terminal connectors in sets of three.
Type
Part Number
Screw-in
170 XTS 001 00
Spring-clip
170 XTS 002 00
Mapping Terminal Blocks
CAUTION
POTENTIAL FOR SHORT CIRCUITS AND/OR POWER-UP SPIKES
Provide external fuses on the operating voltage to protect the module. Appropriate fuse values are shown in the wiring illustration. An unprotected module may be subject to short circuits and/or power-up spikes.
Failure to follow these instructions can result in injury or equipment damage.
Mapping terminal blocks is described in the table below.
Row
Terminal No.
Description
Function
2
4, 8, 12, 16
-
Not used
1, 5, 9, 13
1L+
+24 V actuator power supply output
2, 3, 6, 7, 10, 11, 14, 15
1M-
Actuator power supply neg. 0 V return
17
M-
Module power supply 0 V
18
L+
Module power supply +24V
3
1, 5, 9, 13
OUTI1-, OUTI2-
OUTI3-, OUTI4-
Output current mode (sink)
Channels 1 ... 4
2, 6, 10, 14
OUTI1+, OUTI2+
OUTI3+, OUTI4+
Output current mode (source)
Channels 1 ... 4
3, 7, 11, 15
OUTU1+, OUTU2+
OUTU3+, OUTU4+
Output voltage mode
Channels 1 ... 4
4, 8, 12, 16
-
Not used
17
1M-
Actuator power supply neg. 0 V return
18
1L+
+24 V actuator power supply output
Fuse Required
The 1 A slow-blow fuse shown in the wiring diagram must be wired into the actuator power supply.
Signal Protection
To protect the signal from external noise induced in serial or common mode, we recommend the following precautions.