Safety Class
|
Class 1, IEC 536
|
Safety Type
|
IEC 529: IP20
|
Temperature range (operating)
|
0 ... +60 oC air intake temperature (without forced ventilation). Under more difficult ventilation conditions, power dissipation must be taken into account (refer to the module descriptions).
|
Temperature range (storage)
|
-40 ... +85 oC (without battery)
-40 ... +70 oC (with battery)
|
Relative humidity
|
95 % continuous for 30 days
75 % annual average, noncondensing
|
Atmospheric pressure (operating)
|
>=700 hPa (700 mbar)
|
Atmospheric pressure (transport)
|
>=230 hPa (230 mbar)
|
Pollutants
|
Maximum at 60% relative humidity, noncondensing
S02 <= 0.5 ml/m3
H2S <= 0.1 ml/m3
|
Shock
|
15 g at 147 m/s2 for 11 ms
Three shocks/axis per IEC 68.2-6EC
|
Vibration
|
10...57 Hz @ 0.075mm d.a.57...150Hz @ 1 g per IEC 68.2-27EA
|
Dielectric strength
|
Conforms to IEC 664
|
Norms and Standards
|
CE, UL, CSA, FM
|
Equipment definition
|
Open equipment (IEC 1131-2)
|
Circuits
|
RatedVoltage
|
Fast transients / Burst per IEC61000-4-4
|
---|---|---|
Power mains
|
24 VDC / 230 VAC
|
+/-2 kV
|
BinaryDiscrete inputs
|
24 VDC
230 VAC
|
+/-1 kV
+/-2 kV
|
Analog inputs
|
-
|
+/-1 kV
|
Discrete outputs (electronic)
|
24 VDC
|
+/-1 kV
|
Analog outputs
|
-
|
+/-1 kV
|
Relay outputs
|
24 VDC / 230 VAC
|
+/-1 kV
|
Shielded cables
|
-
|
+/-1 kV
|
Noise immunity to electrostatic discharge
|
+/-4 kV for indirect contact discharge
|
Noise immunity to electromagnetic fields
|
10 V/m
|
RFI suppression
|
Limit curve A
|