Module type
|
16 discrete inputs in 1 group
|
Supply voltage
|
24 VDC
|
Supply voltage range
|
20...30 VDC
|
Supply current consumption
|
max. 250 mA at 24 VDC
|
Power dissipation
|
6 W + ( # of input points on x .144 W)
|
I/O map
|
1 input word
|
Input to input
|
none
|
Field to communication adapter
|
Defined by Communication Adapter type
|
Internal
|
none
|
External: operating voltage
|
1 A slow-blow (Bussmann GDC-1A or equivalent)
|
External: input voltage
|
According to the supply of the connected sensors–not to exceed 4A fast-blow
|
Immunity
|
IEC 1131-2
Surge on auxiliary power supply 500V
|
Emissions
|
EN 50081-2
|
Agency approvals
|
UL, CSA, CE, FM Class 1 Div. 2
|
Width
|
125 mm (4.9 in)
|
Depth (with no adapter)
|
40 mm (1.54 in)
|
Length
|
141.5 mm (5.5 in) no or one busbar
159.5mm (6.3in) two busbars
171.5 mm (6.75in) three busbars
|
Weight
|
190 g (0.42 lb)
|
Number of points
|
16
|
Number of groups
|
1
|
Points per group
|
16
|
Signal type
|
True High
|
IEC 1131 type
|
1+ (See appendix Input Voltage and Current Thresholds for definitions of IEC input types.)
|
ON voltage
|
+11 ... +30 VDC
|
OFF voltage
|
-3 ... +5 VDC
|
Input current
|
2.5 mA minimum ON (6 mA at 24 VDC 1.2 mA maximum OFF
|
Input voltage range
|
-3 ... +30 VDC
|
Input resistance
|
4 kOhm
|
Response time
|
2.2 ms OFF to ON
3.3 ms ON to OFF
|