Module type
|
16 analog inputs
|
Input voltage range
|
+/- 10 V, +/- 5 V
|
Input current range
|
4 ... 20 mA
|
Field device output driving capability
|
6K or less
|
Supply voltage
|
24 VDC
|
Supply voltage range
|
20 ... 30 VDC
|
Supply current consumption
|
max. 305 mA at 24 VDC
|
Power dissipation
|
4.95 W typical
5.55 W maximum
|
I/O map
|
16 input words
4 output words
|
Between channels
|
none
|
Between base supply and ground
|
500 VDC, 1 min
|
Between input channels and ground
|
500 VAC, 1 min
|
Internal (not user-replaceable)
|
2 A slow-blow
|
External (recommended)
|
1 A slow-blow (Bussmann GDC-1A or equivalent)
|
Immunity
|
IEC 1131-2
Surge on auxiliary power supply 500 V
|
Emissions
|
EN 50081-2
|
Agency approvals
|
UL, CSA, CE, FM Class 1 Div. 2
|
Width
|
125 mm (4.9 in)
|
Depth (with no adapter)
|
40 mm (1.54 in)
|
Length
|
141.5 mm (5.5 in) no busbar
|
Weight
|
215 g (0.45 lb)
|
Surge tolerance:
input voltage
input current
|
+/- 30 VDC
+/- 25 mA
|
Number of channels
|
16
|
Format of transmitted data
|
full 16 bits signed (2’s complement)
|
Protection
|
polarity inversion
|
Error indication
|
none
|
Common mode rejection
|
250 VAC @ 47 ... 63 Hz or 100 VDC channel-to-ground
|
Update time for the inputs (in ms)
|
1 + 1.5 xn n = number of declared channels
|
Filtering
|
low pass with cutoff frequency 10 kHz
|
Maximum Sensor Impedance In
|
6K ohms with AAI 14000 at PV02
|
Voltage Mode
|
1.5K ohms with AAI 14000 at PV01
|
Range
|
+/- 10 V
|
+/- 5 V
|
4 ... 20 mA
|
---|---|---|---|
Input impedance
|
20 MOhm
|
20 MOhm
|
250 Ohm
|
Error at 25 deg. C
|
0.27% PE*
|
0.21% PE*
|
0.28% PE*
|
Error at 60 deg. C
|
0.32% PE*
|
0.26% PE*
|
0.38% PE*
|
Temperature drift (60 deg. C)
|
14 ppm PE*/ deg. C
|
14 ppm PE*/ deg. C
|
30 ppm PE*/ deg. C
|
Resolution
|
14 bits + sign
|
14 bits + sign
|
15 bits
|