Module type
|
16 discrete outputs in 2 groups (8 points/group)
|
Supply voltage
|
120 VAC
|
Supply voltage range
|
85 ... 132 VAC @ 47...63Hz
|
Supply current consumption
|
125 mA
|
Power dissipation
|
5 W + (# of output points on x .75 W)
|
I/O map
|
1 output word
|
Point to point
|
none
|
Group to group
|
none
|
Field to communication adapter
|
1780 VAC
|
Internal (replaceable)
|
5 A slow-blow (Wickmann 195150000 or equivalent)
|
Internal (non-replaceable)
|
200 mA slow-blow
|
External (field power)
|
10 A slow-blow (Wickmann 195210000 or equivalent)
|
External (module power)
|
200 mA slow-blow (Wickmann 195020000 or equivalent)
|
Immunity
|
IEC 1131-2
Surge on auxiliary power supply 2 KV
|
Emissions
|
EN 50081-2
|
Agency approvals
|
UL, CSA, CE
FM Class 1, Div. 2
|
Width
|
125 mm (4.9 in)
|
Depth (with no adapter)
|
52 mm (2.05 in)
|
Length
|
141.5 mm (5.5 in) no or one busbar
159.5mm (6.3in) two busbars
171.5 mm (6.75in) three busbars
|
Weight
|
284 g (10 oz)
|
Number of points
|
16
|
Number of groups
|
2 fuse groups, non-isolated
|
Points per group
|
8
|
Output supply voltage
|
120 AC
|
Output supply voltage range
|
85 ... 132 VAC
|
Output voltage
|
External supply - 1.5 VAC
|
Surge voltage
|
300 VAC for 10 s
400 VAC for 1 cycle
|
On state voltage drop
|
1.5 VAC max @ 0.5 A
|
Output (load) current
|
0.5 A/point (see derating curve in next section)
4 A/group
8 A/module
|
Minimum output current
|
30 mA
|
Maximum surge current (rms)
|
15 A/point, one cycle
10 A/point, two cycle
5 A/point, three cycle
|
Output protection
|
RC snubber
|
Signal type
|
True High
|
Leakage current
|
1.9 mA @ 120 VAC max
|
Applied dV / dT
|
400 V / microsecond
|
Response time
|
.5 of one line cycle max OFF to ON
.5 of one line cycle max ON to OFF
|