Module type
|
32 discrete outputs in 2 groups (16 pts/group)
|
Supply voltage
|
24 VDC
|
Supply voltage range
|
20...30 VDC
|
Supply current consumption
|
max. 250 mA at 24 VDC
|
Power dissipation
|
6 W + (# of output points on x .25 W)
|
I/O map
|
2 output word
|
Output group to output group
|
none
|
Field to communication adapter
|
Defined by communication adapter type
|
Internal
|
none
|
External: operating voltage
|
1 A slow-blow (Bussmann GDC-1A or equivalent)
|
External: output voltage
|
According to the supply of the connected actuators–not to exceed 8 A slow-blow/ group
|
Immunity
|
IEC 1131-2
Surge on auxiliary power supply 500 V
|
Emissions
|
EN 50081-2
|
Agency approvals
|
UL, CSA, CE, FM Class 1 Div. 2 pending
|
Width
|
125 mm (4.9 in)
|
Depth (with no adapter)
|
40 mm (1.54 in)
|
Length
|
141.5 mm (5.5 in) no or one busbar
159.5mm (6.3in) two busbars
171.5 mm (6.75in) three busbars
|
Weight
|
210 g (0.46 lb)
|
Output type
|
Solid state switch
|
Output supply voltage
|
24 VDC
|
Output supply voltage range
|
20 ... 30 VDC
|
Output voltage
|
External supply - .5 VDC
|
Number of points
|
32
|
Number of groups
|
2
|
Points per group
|
16
|
Current capacity
|
0.5 A/point maximum
8 A/group
16 A/module
|
Signal type
|
True High
|
Leakage current (output out)
|
< 1 mA @ 24 VDC
|
Surge (inrush) current
|
5 A for 1 ms
|
On state voltage drop
|
< 0.5 VDC @ 0.5 A
|
Fault sensing
|
Outputs are electronically safeguarded to assist in short circuit and overload protection
|
Fault reporting
|
1 red LED/point (row 3) ON when short current/ overload occurs
|
Error indication
|
Output overload for at least one out put (I/O-Error) to communication adapter
|
Response time
(resistive load / 0.5 A)
|
< 0.1 ms OFF to ON
< 0.1 ms ON to OFF
|
Maximum switching cycles
|
1000/h for 0.5 A inductive load
100/s for 0.5 A resistive load
8/s for 1.2 W Tungsten load
|