Module type
|
16 discrete inputs in 1 group
8 discrete outputs in 2 groups (4 pts/group)
|
Supply voltage
|
24 VDC
|
Supply voltage range
|
20...30 VDC
|
Supply current consumption
|
max. 250 mA at 24 VDC
|
Power dissipation
|
6 W + ( # of input points on x .144 W) + (# of output points on x 1 W) )
|
I/O map
|
1 input word
1 output word
|
Input to input
|
none
|
Output group to output group
|
500 VAC
|
Input to output group
|
500 VAC
|
Field to communication adapter
|
Defined by communication adapter type
|
Internal
|
none
|
External: operating and input voltage
|
According to the supply of the connected sensors–not to exceed 4A fast-blow
|
External: output voltage
|
According to the supply of the connected actuators–not to exceed 8 A slow-blow
|
Immunity
|
IEC 1131-2
Surge on auxiliary power supply 500V
|
Emissions
|
EN 50081-2
|
Agency approvals
|
UL, CSA, CE, FM Class 1 Div. 2 pending
|
Width
|
125 mm (4.9 in)
|
Depth (with no adapter)
|
40 mm (1.54 in)
|
Length
|
141.5 mm (5.5 in) no or one busbar
159.5mm (6.3in) two busbars
171.5 mm (6.75in) three busbars
|
Weight
|
220 g (0.49 lb)
|
Number of points
|
16
|
Number of groups
|
4
|
Points per group
|
4
|
Signal type
|
True High
|
IEC 1131 type
|
1+ (See Appendix Input Voltage and Current Thresholds for definitions of IEC input types.)
|
ON voltage
|
+11 ... +30 VDC
|
OFF voltage
|
-3 ... +5 VDC
|
Input current
|
2.5 mA minimum ON (6 mA at 24 VDC)
1.2 mA maximum OFF
|
Input voltage range
|
-3 ... +30 VDC
|
Input resistance
|
4 kOhm
|
Response time
|
2.2 ms OFF to ON
3.3 ms ON to OFF
|
Output type
|
Solid state switch
|
Output supply voltage
|
24 VDC
|
Output supply voltage range
|
20 ... 30 VDC
|
Output voltage
|
External supply - .5 VDC
|
Number of points
|
8
|
Number of groups
|
2
|
Points per group
|
4
|
Current capacity
|
2 A/point maximum
8 A/group
16 A/module
|
Signal type
|
True High
|
Leakage current (output out)
|
< 1 mA @ 24 VDC
|
Surge (inrush) current
|
2.8 A for 10 s max.
|
On state voltage drop
|
< 0.5 VDC @ 2 A
|
Fault sensing
|
Outputs are electronically safeguarded to assist in short circuit and overload protection
|
Fault reporting outputs
|
1 red LED/point (row 3) ON when overload occurs
|
Fault reporting input voltage
|
1 red LED (row 3) signals the state of 4 inputs belonging to the input power supply group
|
Error indication
|
In the event of an overload for on least 1 output, for a short-circuit or overload in one of the 4 encoder supply groups, (I/O-Error) to communication adapter
|
Response time
(resistive load / 2 A)
|
< 0.1 ms OFF to ON
< 0.1 ms ON to OFF
|
Maximum switching cycles
|
1000/h for 2 A inductive load (for inductances > 100 mH and switching currents > 1A, a clamping diode must be installed
100/s for 2 A resistive load
10/s for 1.2 W Tungsten load (when the startup-current factor <= 10 the nominal current)
|