Field Wiring Guidelines
Original instructions
Overview
This section contains wiring guidelines and precautions.
Required Terminal Connector
To connect field devices to the I/O base, you need a field wiring terminal connector. Schneider Electric sells terminal connectors in sets of three.
Type
Part Number
Screw-in
170 XTS 001 00
Spring-clip
170 XTS 002 00
Mapping Terminal Blocks
CAUTION
POTENTIAL FOR SHORT CIRCUITS AND/OR POWER-UP SPIKES
Provide external fuses on the operating voltage to protect the module. Appropriate fuse values are shown in the wiring illustration. An unprotected module may be subject to short circuits and/or power-up spikes.
Failure to follow these instructions can result in injury or equipment damage.
Mapping terminal blocks are described in the table below.
Row
Terminal No.
Description
Function
2
1, 3, 5, 7, 9,11, 13, 15
InU1 ... InU8
Voltage input, channel 1 ... 8
2, 4, 6, 8, 10, 12, 14, 16
InI1 ... InI8
Current input, channel 1 ... 8
17
M-
- return (of operating voltage)
18
L+
+ 24 VDC Operating voltage
3
1, 3, 5, 7, 9,11, 13, 15
Agnd1 ... Agnd8
Analog ground, channel 1 ... 8
2, 4, 6, 8, 10, 12, 14, 16
Inl1 ... Inl8
Current input, channel 1 ... 8
Signal Protection
To protect the signal from external noise induced in serial or common mode, we recommend the following precautions.